open the System Schröders - door
Technical drawing  TSN-12 CE

Fire resistance door European standard class EI

System Schröders TSN-12 CE

Double-leaf fire resistance Steel Door or Gate EI290-Sa4-C5 according to EN 16304

CE-Zeichen labelled

Fire resistance

EI290-Sa4 tested according to EN 1634-1

  • as gate according to DIN EN 13241
  • as external door according to DIN EN 14351-1
Thermal transmittance

UD-value ≥ 1.5 W/(m²K) according to EN ISO 10077-1

Combinable with additional performance characteristics:

Smoke control
(optional)

S200 tested according to EN 1634-3

Burglar resistance
(optional)

RC4 - expert report No. 22-7/15.125, PIV-Velbert
RC3 - expert report No. 22-6/15.125, PIV-Velbert
RC2 - expert report No. 45-48/22.122, PIV-Velbert
RC1 - expert report No. 45-48/22.122, PIV-Velbert

according to DIN EN 1627 ff

Acoustic performance
(optional)

up to RW (C;Ctr) = 48 (-1;-5) dB

according to EN ISO 10140-1 / EN ISO 10140-2 / EN ISO 717

proof of acoustic performance for security doors
(measurement reports, test reports, expert opinions)

Airtightness
(optional)

up to class 3 according to EN 12207 (± 600 Pa)

expert report No. 40-40/12.122, PIV Velbert
Resistance to wind load
(optional)

up to class C4 according to EN 12210 (± 1.600 Pa)

expert report No. 40-40/12.122, PIV Velbert
Watertightness
(optional)

up to class 4A according to EN 12208 (± 150 Pa)

expert report No. 40-40/12.122, PIV Velbert
Resistance to positive and negative pressure
(optional)

according to DIN EN 12211 (up to 3,800 Pa)

expert report No. 40-52/16.120
Behavior between different climates
(optional)

class 2 (d + e) according to EN 12219 (deflection)

Ability to release
(optional)

according to DIN EN 16034
hold-open device according to DIN EN 14637

according to DIN EN 14351-1
proven for doors in escape and rescue routes

Flush with surface
(optional)

flush-mounted design FLAT

Explosion protection
(optional)
Logo ATEX For installation in potentially explosive areas, please see confirmation letter Explosion protection ATEX for hinged doors System Schröders (in German language) (PDF)
Technical description
Dimensions
(rough building dimension)
width from 1,250 mm up to 3,250 mm
heigth from 1,700 mm up to 2,950 mm

deviating special sizes possible with corresponding individual proof under building law
Door leaf

leaf thickness 68 mm to 69 mm - smooth double-walled
plate thickness 1.0 mm to 1.5 mm

  • thin rebate
    • optional thick rebate
    • insulating insert
      • optional full-face glued and pressed with cover plate,
        thus particularly smooth and even door leaf

securing pins

Frame frame-system "ZNG"

with flush clipped in Thelesol® fire protection strips and elastic rubber seal

corner frame

  • optional enclosing frame
  • optional block frame
Floor seal required for smoke control, acoustic performance, Airtightness
Glazing
(optional)

glass dimensions and -form variable
(rectangular glazing max. 980 mm x 2,180 mm)

minimum frieze width: 150 mm

  • optional with intermediate glass inset bars
  • optional with port-hole

glass inset bars with concealed screw connection (for rectangular glazing)

Hinges

2/3-part KO door hinges per leaf
with patented easy-running bearings as Easy-running doors
or with ball-Bearing spacer rings

  • optional door hinge with 3D adjustment
Fittings
  • optional any approved handle set according to EN 1906 resp. EN 179
  • optional panic bar handle or push bar according to EN 1125

for RC version: ES-1 to ES-3 security fittings

Locking active leaf

profile cylinder prepared (cylinder on-site)

single locking according to EN 12209, depending on version multi-point locking

fixed leaf

internal snap bolt (locking upwards)
depending on version, with locking upwards and downwards (rebate shoot bolt, shoot bolt lock)

  • optional panic locking according to EN 179 resp. EN 1125
Self closing

both leafs with door closer according to DIN EN 1154
with door closing sequence control according to EN1158

Installation
  • in masonry(thk ≥ 175 mm)
  • in concrete(thk ≥ 140 mm)
  • in aerated concrete(thk ≥ 150 mm)
  • in mounting walls min. F90 (thk ≥ 100 mm)
  • in encased steel columns min. F90 (thk ≥ 140 mm)
  • in timber stud walls min. F90 (thk ≥ 120 mm)
  • optional blunt installation in soffit
  • optional installation on the wall plate
  • approved for installation at great heights (installation not at floor level: height on one or both sides > 500 mm above ground level - e.g. as manhole door/flap) with lower fire and smoke seal - also thresholdless
Label

CE-Zeichen labelling and declaration of performance

Optional
  • additional security devices possible
    (magnetic contact, bolt contact, e-opener...)
  • hold-open system in according to DIN EN 14637
  • stainless steel design

The information provided relates to standard equipment variants. When combining different performance characteristics, customised equipment may be required.