open the System Schröders - door

ModulSystem Schröders

Hinged fire doors and gates European standard
ModulSystem Schröders Fire resistance Smoke control Bullet resistance Burglar resistance Acoustic performance Airtightness
wind load
watertightness
Positive and negative pressure
Type Leaves Dimensions
width x height (mm)
Flat Resistance class Designation Class Resistance class Insulation values Class  
EIS-1/60 1
from 625  x  1,750
to 1,500  x  3,000
✔ EI2 60
E 120
EW 60
(120 min. tested)
Sa4 / S200 - - - airtight up to 4
wind up to C5
rain up to 8A
up to 5,000 Pa
EIS-2/60 2
from 1,275  x  1,875
to 3,000  x  3,000
✔ EI2 60
E 120
EW 60
(120 min. tested)
Sa4 / S200 - - - airtight up to 3
wind up to C4
rain up to 3A
up to 3,800 Pa
EIS-11 1
from 500  x  750
to 1,400  x  2,650
✔ EI2120-Sa4-C5 S200 - RC2, RC1 - airtight up to 4
wind up to C5
rain up to 8A
up to 5,000 Pa
TSN-1 CE 1
from 525  x  500
to 2,300  x  4,600
✔ EI230-Sa4-C5 S200 up to FB6 RC4, RC3, RC2, RC1 up to
RW(C;Ctr)
= 53 (-1;-5) dB
airtight up to 4
wind up to C5
rain up to 8A
up to 5,000 Pa
TSN-2 CE 2
from 1,250  x  1,900
to 4,600  x  4,600
✔ EI230-Sa4-C5 S200 up to FB6 RC4, RC3, RC2, RC1 up to
RW(C;Ctr)
= 48 (-1;-5) dB
airtight up to 3
wind up to C4
rain up to 3A
up to 3,800 Pa
TSN-3 CE 1
from 525  x  750
to 1,750  x  3,500
✔ EI260-Sa4-C5 S200 - RC4, RC3, RC2, RC1 up to
RW(C;Ctr)
= 53 (-1;-5) dB
airtight up to 4
wind up to C5
rain up to 8A
up to 5,000 Pa
TSN-4 CE 2
from 1,375  x  1,750
to 3,500  x  3,500
✔ EI260-Sa4-C5 S200 - RC4, RC3, RC2, RC1 up to
RW(C;Ctr)
= 48 (-1;-5) dB
airtight up to 3
wind up to C4
rain up to 3A
up to 3,800 Pa
TSN-11 CE 1
from 525  x  750
to 1,500  x  2,950
✔ EI290-Sa4-C5 S200 - RC4, RC3, RC2, RC1 up to
RW(C;Ctr)
= 53 (-1;-5) dB
airtight up to 4
wind up to C5
rain up to 8A
up to 5,000 Pa
TSN-12 CE 2
from 1,375  x  1,750
to 3,250  x  3,250
✔ EI290-Sa4-C5 S200 - RC4, RC3, RC2, RC1 up to
RW(C;Ctr)
= 48 (-1;-5) dB
airtight up to 3
wind up to C4
rain up to 3A
up to 3,800 Pa
ES-1/60 1
max
1,580 x 3,100
✔ E 60
EW 60
- - - - - up to 5,000 Pa
ES-2/60 2
max
3,100 x 3,100
✔ E 60
EW 60
- - - - - up to 3,800 Pa
ES-1/120 1
max
1,580 x 3,100
✔ E 120
EW 60
- - - - - up to 5,000 Pa
ES-2/120 2
max
3,100 x 3,100
✔ E 120
EW 60
- - - - - up to 3,800 Pa
ES-1/180 1
max
1,580 x 3,100
✔ E 180
EW 60
- - - - - up to 5,000 Pa
ES-2/180 2
max
3,100 x 3,100
✔ E 180
EW 60
- - - - - up to 3,800 Pa
ES-1/240 1
max
1,580 x 3,100
✔ E 240
EW 60
- - - - - up to 5,000 Pa
ES-2/240 2
max
3,100 x 3,100
✔ E 240
EW 60
- - - - - up to 3,800 Pa
Hinged steel fire doors British standard
Tested according to BS 476, part 22 Fire-resistance tested at:
Warrington
Designation Leaves Dimensions
width x height
Flat Resistance Certificate optional
glazing
optional
stainless steel
BSN-1/60 1
max
1,300 x 2,600
- 60 minutes WFRC No. C103480 yes yes
BSN-2/60 2
max
2,600 x 2,600
- 60 minutes WFRC No. C103484 yes yes
BSN-1/120 1
max
1,300 x 2,600
- 120 minutes WFRC No. C103481 yes yes
BSN-2/120 2
max
2,600 x 2,600
- 120 minutes WFRC No. C103485 yes yes
BSN-1/180 1
max
1,300 x 2,600
- 180 minutes WFRC No. C103482 yes yes
BSN-2/180 2
max
2,600 x 2,600
- 180 minutes WFRC No. C103486 - yes
BSN-1/240 1
max
1,300 x 2,600
- 240 minutes WFRC No. C103483 - yes
BSN-2/240 2
max
2,600 x 2,600
- 240 minutes WFRC No. 102034 - yes

Explanation of the chart

  • The chart shows possible combinations of different performance requirements.
  • The standard performance requirement for each door type is shown in bold. The other performance requirements listed can be added to the relevant door type if required.
  • Please click on the relevant door type to view the detailed product descriptions.
  • Approvals, test certificates, technical drawings, tender documents and product brochures can be found under the relevant door type.
  • The range of dimensions may vary when combining different performance requirements.