Fire resistance door European standard class EI
| System Schröders TSN-1 CE | |
|---|---|
Single-leaf fire resistance steel door or flap EI230-Sa4-C5 according to EN 16304 |
|
|
|
|
| Fire resistance |
EI230-Sa4 tested according to EN 1634-1
|
| Thermal transmittance |
UD-value ≥ 1.3 W/(m²K) according to EN ISO 10077-1 |
Combinable with additional performance characteristics: |
|
| Smoke control
(optional) |
S200 tested according to EN 1634-3 |
|
Bullet resistance
(optional) |
class FB6 - test report S-23-0208-04/05 Beschussamt Ulm |
| Burglar resistance
(optional) |
RC4 - expert report No. 22-5/15.125, PIV-Velbert
according to DIN EN 1627 - 1630 |
| Acoustic performance
(optional) |
up to RW (C;Ctr) = 53 (-1;-5) dB according to EN ISO 10140-1 / EN ISO 10140-2 / EN ISO 717 |
| Airtightness
(optional) |
up to class 4 according to EN 12207 (± 600 Pa) expert report 40-14/26, PIV Velbert |
| Resistance to wind load
(optional) |
up to class C5 according to EN 12210 (± 2.000 Pa) expert report 40-14/26, PIV Velbert |
| Watertightness
(optional) |
up to class 8A according to EN 12208 (+ 450 Pa) expert report 40-14/26, PIV Velbert |
| Resistance to positive and negative pressure
(optional) |
according to DIN EN 12211 (up to 5,000 Pa) expert report No. 16-003037-PR01 |
| Behavior between different climates
(optional) |
class 2 (d + e) according to EN 12219 (deflection) |
| Ability to release
(optional) |
according to DIN EN 16034
according to DIN EN 14351-1 |
| Flush with surface
(optional) |
|
| Explosion protection
(optional) |
For installation in potentially explosive areas, please see confirmation letter Explosion protection ATEX for hinged doors System Schröders (in German language) (PDF)
|
| Technical description | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
Dimensions
(rough building dimension) |
|
|||||||||
| Dimensions flap
(rough building dimension) |
|
|||||||||
| Door leaf |
leaf thickness 68 mm to 69 mm - smooth double-walled
securing pins |
|||||||||
| Frame | frame-system "ZNG"
with flush clipped in Thelesol® fire protection strips and elastic rubber seal corner frame
|
|||||||||
| Floor seal | required for smoke control, acoustic performance, Airtightness
|
|||||||||
| Glazing
(optional) |
glass dimensions and -form variable minimum frieze width: 130 mm
glass inset bars with concealed screw connection (for rectangular glazing) |
|||||||||
| Hinges |
2/3-part KO door hinges
|
|||||||||
| Fittings |
for RC version: ES-1 to ES-3 security fittings |
|||||||||
| Locking |
single locking according to EN 12209, depending on version multi-point locking
|
|||||||||
| Self closing |
door closer according to DIN EN 1154
|
|||||||||
| Installation |
|
|||||||||
| Label |
|
|||||||||
| Optional |
|
|||||||||
|
The information provided relates to standard equipment variants. When combining different performance characteristics, customised equipment may be required. The licensed System Schröders manufacturers will be happy to consult you on planning your requirements. |
||||||||||
For installation in potentially explosive areas, please see confirmation letter