Fire resistance door class EI
| System Schröders EIS-11 | |
|---|---|
Single-leaf fire resistance door EI2 120 / E 120 / EW 60 (Sa) |
|
| Fire resistance | EI2 120 / E 120 / EW 60
tested in accordance with EN 1634-1 classification report WFRC 360408 according to EN 13501-2 |
| Smoke protection
(optional) |
Sa tested according to EN 1634-3
classification report WFRC 360408 according to EN 13501-2 |
| Thermal transmittance
(optional) |
UD-Wert ≥ 2.7 W/(m²K) according to EN ISO 10077-1 |
| Airtightness
(optional) |
according to EN 12207, up to class 4 |
| Resistance to wind load
(optional) |
according to EN 12210, up to class C5 |
| Watertightness
(optional) |
according to EN 12208, up to class 8A |
| Ability to release
(optional) |
|
| Resistance to positive and negative pressure
(optional) |
up to 5,000 Pa |
| Technical data | |||||||
|---|---|---|---|---|---|---|---|
| Dimensions
Standard dimensions |
|
||||||
| Door leaf | Leaf thickness 68 / 69 mm - smooth, double-walled, galvanized or optional stainless steel
plate thickness up to 1.5 mm
|
||||||
| Door frame | Door frames „System Schröders“
(see installation variants) optional with elastic smoke protection seal corner frame profile, three, or optional four sided wraparound frame option |
||||||
| Floor seal | Required for smoke protection, increased air tightness, driving rain tightness
|
||||||
| Lock options | Latch lock according to EN 12209
profile cylinder prefab (cylinder on-site)
|
||||||
| Hardware / fittings |
door closer according to EN 1154
2/3-part KO door hinges
for smaller doors, optional with spring hinge
|
||||||
| Installation |
|
||||||
|
|||||||
| Options |
|
||||||